This paper proposes the use of a least mean fourth (LMF)-based algorithm for single-stage three-phase grid-integrated solar photovoltaic (SPV) system. It consists of an SPV array, voltage source converter (VSC), three-phase grid, and linear/nonlinear loads. This system has an SPV array coupled with a VSC to provide three-phase active power and also acts as a static compensator for the reactive power compensation. It also conforms to an IEEE-519 standard on harmonics by improving the quality of power in the three-phase distribution network. Therefore, this system serves to provide harmonics alleviation, load balancing, power factor correction and regulating the terminal voltage at the point of common coupling. In order to increase the efficiency and maximum power to be extracted from the SPV array at varying environmental conditions, a single-stage system is used along with perturb and observe method of maximum power point tracking (MPPT) integrated with the LMF-based control technique. The proposed system is modeled and simulated using MATLAB/Simulink with available simpower system toolbox and the behaviour of the system under different loads and environmental conditions are verified experimentally on a developed system in the laboratory.

Authors (2) 2 from IIT Delhi
Publication Details
TypeJournal Article
PublishedApril 13, 2016
Source IEEE Transactions on Sustainable Energy
PublisherInstitute of Electrical and Electronics Engineers
Volume/Issue Vol. 7 , Issue 4 , pp. 1379-1387
DOI 10.1109/tste.2016.2553181
OpenAlex ID W2337006197
Open AccessClosed Access
Sustainable Development Goals
7 7 9 9