Video
Loading video...

📄 Journal Article

Symmetrical Components-Based Modified Technique for Power-Quality Disturbances Detection and Classification

March 01, 2016 74 citations 🔒 Closed IEEE Transactions on Industry Applications
74
Citations
3
Authors
23
References
1
Countries
Abstract

This paper presents a modified approach based on symmetrical components in time domain for the detection and classification of various power-quality (PQ) disturbances. Single-phase PQ disturbance signal along with the two other ideal phases generated using phase-locked loop (PLL) is processed to find out the symmetrical components of all phases in time domain. Triggering points for PQ disturbances have been detected from the negative-sequence component of disturbance phase and have been easily classified from the signatures of the waveforms using the summation of the positive- and negative-sequence components. PQ disturbances, such as voltage sag, swell, interruption, harmonics, flicker, transients, notches, and spike present in a distribution system, have been investigated and are easily localized and segmented with this technique. Being a time-domain technique, it can be adopted for the online monitoring and assessment of the PQ disturbances. Simulated and real-time results are presented for a number of PQ disturbances to show the effectiveness of the proposed method for the PQ disturbances’ detection and classification.

Publication Details
TypeJournal Article
PublishedMarch 01, 2016
Source IEEE Transactions on Industry Applications
PublisherInstitute of Electrical and Electronics Engineers
Volume/Issue Vol. 52 , Issue 4 , pp. 3443-3450
DOI 10.1109/tia.2016.2536665
OpenAlex ID W2330830656
Open AccessClosed Access
Sustainable Development Goals
9 9