Load Compensation for Diesel Generator-Based Isolated Generation System Employing DSTATCOM
This paper presents the control of distribution static synchronous compensator (DSTATCOM) for reactive power, harmonics and unbalanced load current compensation of a diesel generator set for an isolated system. The control of DSTATCOM is achieved using least mean square-based adaptive linear element (Adaline). An Adaline is used to extract balanced positive-sequence real fundamental frequency component of the load current and a proportional–integral (PI) controller is used to maintain a constant voltage at the dc-bus of a voltage-source converter (VSC) working as a DSTATCOM. Switching of VSC is achieved by controlling source currents to follow reference currents using hysteresis-based PWM control. This scheme is simulated under MATLAB environment using Simulink and PSB block-set toolboxes for feeding linear and nonlinear loads. The modeling is performed for a three-phase, three-wire star-connected synchronous generator coupled to a diesel engine, along with the three-leg VSC working as a DSTATCOM. Results are presented to verify the effectiveness of the control of DSTATCOM for the load compensation and an optimal operation of the DG set.
| Type | Journal Article |
|---|---|
| Published | November 10, 2010 |
| Source | IEEE Transactions on Industry Applications |
| Publisher | Institute of Electrical and Electronics Engineers |
| Volume/Issue | Vol. 47 , Issue 1 , pp. 238-244 |
| DOI | 10.1109/tia.2010.2090847 |
| OpenAlex ID | W2140526883 |
| Open Access | Closed Access |