Video
Loading video...

📄 Journal Article

Automatic generation control of an interconnected hydrothermal system in continuous and discrete modes considering generation rate constraints

January 01, 1983 118 citations 🔒 Closed IEE Proceedings D Control Theory and Applications
118
Citations
2
Authors
2
References
1
Countries
Abstract

The paper deals with some aspects of automatic generation control of the two-area hydrothermal system provided with classical controllers. A comprehensive procedure for continuous-and discrete-mode optimisation of integral controllers using an integral squared error criterion is suggested. Investigations reveal that the optimal integral gains achieved through continuous-mode analysis are totally unacceptable in the discrete mode for the sampling periods used in practice. Moreover, for all practical purposes, the optimum integral gains in the discrete mode can be achieved by neglecting the generation rate constraints from the mathematical model, in contrast to the case in the continuous mode. Analysis also highlights significant differences in the dynamic performance of the hydrothermal system due to step-load perturbation in either of the areas. An attempt is also made to recommend an optimum sampling period.

Authors (2) 2 from IIT Delhi
Publication Details
TypeJournal Article
PublishedJanuary 01, 1983
Source IEE Proceedings D Control Theory and Applications
Volume/Issue Vol. 130 , Issue 1 , pp. 17-17
DOI 10.1049/ip-d.1983.0004
OpenAlex ID W2139470852
Open AccessClosed Access
Sustainable Development Goals
7 7