Video
Loading video...

📄 Journal Article

Dynamics and stability of wind and diesel turbine generators with superconducting magnetic energy storage unit on an isolated power system

January 01, 1991 95 citations 🔒 Closed IEEE Transactions on Energy Conversion
95
Citations
2
Authors
14
References
1
Countries
Abstract

Dynamic system analysis is carried out on an isolated electric power system consisting of a diesel generator and a wind-turbine generator. The 150 kW wind turbine is operated in parallel with a diesel generator to serve an average load of 350 kW. A comprehensive digital computer model of the interconnected power system including the diesel and wind-power dynamics with a superconducting magnetic energy storage (SMES) unit is developed. Time-domain solutions are used to study the performance of the power system and control logic. Based on a linear model of the system, it is shown that changes in control-system settings could be made to improve damping and optimization of gain parameters and stability studies are done using the Lyapunov technique and eigenvalue analysis. The effect of introducing the SMES unit for improvement of stability and system dynamic response is studied.>

Authors (2) 2 from IIT Delhi
Publication Details
TypeJournal Article
PublishedJanuary 01, 1991
Source IEEE Transactions on Energy Conversion
PublisherInstitute of Electrical and Electronics Engineers
Volume/Issue Vol. 6 , Issue 4 , pp. 579-585
DOI 10.1109/60.103628
OpenAlex ID W2136825749
Open AccessClosed Access
Sustainable Development Goals
7 7 9 9